Beckett · Boiler
Red light flashing Soft lockout - no flame proved
What the control is telling you
Flashing red means a normal safety lockout. Either no flame was seen before the trial-for-ignition time ran out, or the cad cell already saw light when the oil valve was about to open.
Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)
Likely causes
- No oil at the nozzle: tank empty, valve closed, plugged filter or strainer, air in the pump
- Plugged or wrong nozzle, low pump pressure
- Electrodes out of adjustment or weak igniter
- Dirty cad cell or high cad cell resistance
- Stray light reaching the cad cell during valve-on delay
Test and repair steps
- Before any reset look in the chamber. If oil has pooled or the boiler is full of oil vapor, shut off power and oil, let it cool and clean it out first. Never try to relight a hot, vapor-filled chamber.
- Check the oil supply tank level, both shutoff valves open, filter clean. Bleed the pump if air is suspected (see the NX pump prime guide).
- Power off and pull the nozzle line. Check nozzle, electrodes and igniter spring contacts.
- Clean the cad cell lens and check its resistance with flame on (normal is 0 to 1600 ohms).
- Reset by clicking the button once (under 1 second). Reset one time only, then watch the cycle.
- If it keeps locking out it will go to hard lockout (solid red).
Other codes on the same units
- Green light flashing Recycle - flame lost while running
- Green light solid Flame sensed
- Red light solid Restricted (hard) lockout
- Yellow light solid Pump prime mode (or reset held 15 s)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 5 Status Lights p.13; Sequence of Operation p.12. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.