Beckett · Boiler

Green light flashing Recycle - flame lost while running

Medium severity Beckett NX

What the control is telling you

Flashing green means the flame dropped out during the run. The control shut the burner down and is waiting 60 seconds before it tries the ignition sequence again. If it keeps losing flame past the control's set time, it goes to hard lockout instead.

Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

Likely causes

  • Air in the oil line or pump (flame pulses then drops)
  • Partly plugged nozzle or filter
  • Poor combustion setting or draft problem
  • Dirty cad cell or cad cell resistance creeping toward the lockout range
  • Water in the oil

Test and repair steps

  1. Let the 60 s recycle delay run and watch the next start.
  2. Check oil supply and bleed the pump if there are bubbles.
  3. Check cad cell resistance with flame on. The NX lets less light reach the cad cell than older burners, so readings run higher; 0-1600 ohms is normal, above that is the limited range.
  4. Replace the nozzle and line filter if they are old.
  5. Set combustion with an analyzer (see the NX combustion guide).

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 5 Status Lights p.13; Sequence of Operation (Recycle) p.12; cad cell note p.15. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.