Beckett · Boiler
Green light solid Flame sensed
What the display is showing
Solid green is normal while the burner is running: the cad cell sees flame. If it is on while the burner is off in standby, the cad cell is seeing stray light.
Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)
Good to know
- Burner firing normally
- In standby: light leaking onto the cad cell (burner cover off, sight port or room light)
What to do
- During a run, no action needed.
- In standby with green on put the burner cover back on and look for light getting to the cad cell. Stray light at the end of valve-on delay will cause a lockout.
Other codes on the same units
- Green light flashing Recycle - flame lost while running
- Red light flashing Soft lockout - no flame proved
- Red light solid Restricted (hard) lockout
- Yellow light solid Pump prime mode (or reset held 15 s)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 5 Status Lights p.13. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.