Rheem · Heat pump · Defrost

Demand defrost cycle

PRL-JECICC control

What happens, in order

  1. In heat mode the ICC watches outdoor coil temperature, ambient temperature and compressor run time
  2. Defrost starts when the coil is below 35 F, the compressor has run at least 34 minutes with the coil below 35 F, and the algorithm decides a defrost is needed
  3. A defrost is also forced after 6 hours of accumulated compressor run time with no defrost and the coil below 35 F
  4. Display shows lowercase d during defrost
  5. Low pressure control is ignored while defrost runs
  6. Defrost ends when the coil reaches the terminate temperature or 14 minutes have passed, whichever comes first
  7. Optional noise abatement compressor shuts down for 5 s going into and coming out of defrost (set by communicating thermostat or service tool)
  8. If the ambient sensor fails the ICC starts a defrost every 34 minutes of heating with the coil below 35 F
  9. Test press SW2 for 1 s while running in heat; unit defrosts until termination temperature or 14 min; press SW2 again to end the test

Timings and thresholds

ItemValue
Coil temperature to allow defrostbelow 35 F
Compressor run before defrost34 min
Forced defrost run time6 hours
Max defrost time14 min
Terminate temperature (default)70 F (50, 60, 70 or 80 by dip switch)
Ambient sensor failed interval34 min
Noise abatement pause5 s

Codes you may see during this

d (display)

Applies to: Rheem PRL-JEC heat pump

Models

PRL-JEC

More Rheem heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: PRL-JEC heat pump installation instructions, section 8 Demand Defrost Control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.