Midea · Heat pump · Defrost

Multi-zone defrost entry and exit

DLCMRBHDLCMHBH multi-zone outdoor

What happens, in order

  1. After the compressor settles into normal running, the lowest T3 reading between minute 10 and minute 15 is stored as T30
  2. Defrost starts if any of these is true 29 min cumulative run and T3 below TCDI1 and T3 plus offset is at or below T30; 35 min run and T3 below TCDI2 with offset; 40 min run and T3 below -24 C for 3 minutes; 120 min run and T3 below -15 C
  3. Four-way valve and fans follow the defrost action profile
  4. Defrost ends when T3 passes the quit temperature, or after 10 minutes, or when the mode changes or the unit is turned off
  5. Heating resumes in normal heating mode

Timings and thresholds

ItemValue
Check window for T30minute 10 to 15
Run time conditions29, 35, 40 or 120 min
Max defrost time10 min
Four-way valve closes after heat stopsafter 2 min compressor off

Applies to: Midea / Carrier / Viessmann DLCMRBH and DLCMHBH multi-zone outdoor units (Vitocal 200-S)

Models

DLCMRBHDLCMHBH

More Midea heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea-Carrier-Viessmann DLCMRBH / DLCMHBH service manual (Viessmann Vitocal 200-S 6225551-03), Defrosting Control; Four-way valve control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.