Midea · Heat pump · Startup

Compressor start and system protections

DLCMRBHDLCMHBH multi-zone outdoor

What happens, in order

  1. First compressor start waits 1 minute; later restarts wait 3 minutes
  2. Indoor/outdoor communication no feedback from the outdoor unit for 2 minutes stops the unit and shows a failure code
  3. Outdoor anti-freeze capacity demand drops to zero when T2 is below 4 C for 250 s or below 0 C; normal running resumes when T2 is above 8 C and at least 3 minutes have passed
  4. Low ambient with the compressor off, T4 below -35 C for 10 s stops the unit and shows LP; with the compressor on, T4 below -40 C for 10 s does the same; it exits when T4 is at or above -32 C for 10 s
  5. Low voltage unit restarts 3 minutes after the protection clears, if voltage returns within that time
  6. Four-way valve is open in heating and closes 2 minutes after the compressor stops when leaving heating; on any fault (except discharge temperature, high or low pressure) it closes immediately

Timings and thresholds

ItemValue
First start delay1 min
Restart delay3 min
Communication loss timeout2 min
Anti-freeze entryT2 under 4 C for 250 s, or under 0 C
Anti-freeze exitT2 above 8 C and 3 min

Codes you may see during this

LP

Applies to: Midea / Carrier / Viessmann DLCMRBH and DLCMHBH multi-zone outdoor units

Models

DLCMRBHDLCMHBH

More Midea heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea-Carrier-Viessmann DLCMRBH / DLCMHBH service manual (Viessmann Vitocal 200-S 6225551-03), Main Protection. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.