Midea · Mini-split · Defrost

Defrost mode

DLFSHB high wall

What happens, in order

  1. Control watches T3, T4 and compressor run time to decide when to defrost
  2. In defrost the compressor keeps running while the indoor and outdoor fans stop
  3. Defrost light on the indoor unit comes on and the defrost symbol shows on the display
  4. Defrost ends and heating resumes when T3 rises above TCDE1, or T3 stays above TCDE2 for 80 s, or the unit has been in defrost for 15 minutes

Timings and thresholds

ItemValue
T3 above TCDE2 hold time80 s
Max defrost time15 min

Codes you may see during this

dF

Applies to: Midea / Carrier DLFSHB high wall indoor unit

Models

DLFSHB

More Midea mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Midea-Carrier DLFSHB service manual MS-DLFSHB-01, Defrosting Mode. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.