Kinghome · Mini-split · Pump/purge

Refrigerant recovery (pump-down) from the remote

KM09-24HT1DIHF1DI

What happens, in order

  1. Within 5 minutes after power-up (unit on or off), press LIGHT three times within 3 seconds
  2. Fo is displayed and recovery starts
  3. Close the liquid valve
  4. After 5 minutes prick the service valve core; if no refrigerant sprays out, close the gas valve at once and switch the unit off
  5. Recovery ends on any remote signal, or automatically after 25 minutes; the unit returns to standby or to its earlier mode

Timings and thresholds

ItemValue
Entry window after power-up5 min
Button presses3 within 3 s
Wait before checking service valve5 min
Automatic exit25 min

Codes you may see during this

Fo

Applies to: Kinghome wall mini-splits KM09-12-18-24HT1DI, KM09-24HF1DI

Models

KM09-24HT1DIKM09-24HF1DI

More Kinghome mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Kinghome KM09-12-18-24HT1DI service manual, 6.2 Brief description of modes and functions; Kinghome KM09-24HF1DI service manual, 6.2 Brief description of modes and functions. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.