Kinghome · Mini-split · Heating

Indoor unit modes: cooling, dry, heating, auto and fan

KM09-24 wall units

What happens, in order

  1. Cooling indoor fan and swing run as set; setpoint 16-30C
  2. If the outdoor unit faults or stops on protection, the indoor unit keeps its previous state and shows the code
  3. Dry indoor fan runs on low, swing as set; protections as in cooling; sleep is not available in dry
  4. Heating on start the indoor unit enters cold-air prevention (blower held back until the coil is warm; remote note says 1-5 minute delay depending on room temperature)
  5. On stop, if the indoor unit was only just running, it enters a residual-heat blowing period
  6. Auto mode standard heating setpoint 20C and standard cooling setpoint 25C; the unit changes mode by room temperature
  7. Fan mode indoor fan runs at the chosen speed; compressor, outdoor fan and 4-way valve stay off
  8. Forced defrost and refrigerant recovery are available from the remote (see separate rows)

Timings and thresholds

ItemValue
Setpoint range16-30C (61-86F)
Cold-air delay (remote note)1-5 min
Auto heating setpoint20C
Auto cooling setpoint25C

Applies to: Kinghome wall mini-splits KM09-12-18HEDI, KM09-12-18-24HT1DI, KM09-24HF1DI

Models

KM09HEDIKM12HEDIKM18HEDIKM09-24HT1DIKM09-24HF1DI

More Kinghome mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Kinghome KM09-12-18HEDI service manual, 6.2 Description of each control operation; Kinghome KM09-12-18-24HT1DI service manual, 6.2 Brief description of modes and functions; Kinghome KM09-24HF1DI service manual, 6.2 Brief description of modes and functions. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.