ICP · Heat pump · Defrost

Heat pump: defrost board interval and defrost timers

N4H3

What happens, in order

  1. Interval is 30, 60 or 90 min (jumper at the board edge, factory 90 min)
  2. The interval timer starts when the contactor is energized with 24 V on T1 and the defrost thermostat is closed at about 32 F; it only counts during heat calls
  3. When the interval ends, the board starts defrost: it runs like cooling, with the outdoor fan off and second-stage (strip) heat on
  4. A separate 10 minute defrost timer (not adjustable) runs only while defrosting; defrost ends when the thermostat opens at about 65 F or the timer ends
  5. Back in heating reversing valve shifts back, outdoor fan starts and strip heat drops out
  6. Test with the defrost thermostat closed, short the SPEEDUP pins; the reversing valve should shift within 1 to 21 s. Remove the short right after it shifts for a short defrost, or hold it more than 2 s after the shift to go straight back to heating

Timings and thresholds

ItemValue
Interval options30 / 60 / 90 min
Interval factory90 min
Defrost timer10 min fixed
Defrost startabout 32 F coil
Defrost endabout 65 F coil
Reversing valve shift on speed-up1 to 21 s

Applies to: ICP N4H3 heat pump

Models

N4H3

More ICP heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ICP N4H3 heat pump installation instructions (428 01 5103), Defrost Control Board and Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.