Goodman · Furnace · Heating

Dual fuel heat pump to gas furnace transition

34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96

What happens, in order

  1. Heat pump runs first on a W call when no balance point lockout is active.
  2. If the call is still present after the target runtime, the heat pump runs an extra stage up percentage, then the system switches to gas heat.
  3. Each transition is recorded as a strike against the heat pump.
  4. After the over target threshold strike count is reached, the heat pump is locked out and the furnace becomes primary heat.
  5. While locked out, the furnace runs low stage gas heat; a satisfied call under the stage down limit adds a strike against the furnace.
  6. After the under target threshold count, the heat pump lockout is removed and the heat pump runs again on the next cycle.

Timings and thresholds

ItemValue
Example target runtime20 minutes
Example stage up 20%extra 4 minutes, switch to gas at 24 minutes
Example stage down 15%furnace satisfying in under 17 minutes counts as a strike

Applies to: Communicating or fossil fuel heat pump with gas furnace

More Goodman furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 26-27, 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.