Goodman · Furnace · Cooling

Cooling airflow ramping profiles A to D

34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96

What happens, in order

  1. Profile A 100% airflow with a 1 minute OFF delay at 100%.
  2. Profile B step to 50% airflow for 30 seconds, ramp to 100%, then a 1 minute OFF delay at 100%.
  3. Profile C ramp to 85% airflow for about 7 1/2 minutes, step to 100%, then a 1 minute OFF delay at 100%.
  4. Profile D 50% airflow for 1/2 minute, then 85% for about 7 1/2 minutes, then 100%, with a 1/2 minute OFF delay at 50%.

Timings and thresholds

ItemValue
Profile A OFF delay1 minute at 100%
Profile B 50% step30 seconds
Profile C 85% runabout 7 1/2 minutes
Profile D OFF delay1/2 minute at 50%

Applies to: Multi-speed circulator blower, cooling

More Goodman furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 28. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.