Won't start, hums or trips overload

What is going on

Possible causes and checks for: won't start, hums or trips overload.

Likely causes

  • Open start winding or start relay (no pause at combined start+run wattage)
  • Failed start/run capacitor
  • Current relay not level/stuck
  • Potential relay wrong rating
  • PTC relay not cooled (2–5 min)
  • Starting against unequalized pressures with PSC/split-phase motor
  • Stuck rotor (long idle, plating, liquid refrigerant)
  • Low voltage

Check in this order

  1. Wattmeter start signature (B84)
  2. Discharge + test caps (ohm swing test and µF)
  3. Check relay per C8/C9
  4. Verify voltage
  5. Ohm C–R, C–S, R–S vs table A23
  6. Megger to ground
  7. If all electrical tests pass → hard start kit (B95)

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.