KeepRite · Heat pump troubleshooting
Outdoor unit will not run or will not defrost - KeepRite heat pump defrost board (FAST 1173636/1177927/1190281)
What is going on
Checks on the time/temperature defrost board used in these heat pumps.
Likely causes
- No 24 V on Y from the thermostat
- Open pressure switch
- Bad contactor
- No 24 V on T1
- Defrost thermostat stuck
- Bad pigtail harness
Check in this order
- Unit will not run check 24 V at the Y input, then at the Y spade (goes out through the pressure switches to the contactor).
- Y spade has 24 V but the contactor is open: check coil voltage; none means an open pressure switch, voltage present means a bad contactor.
- Contactor closed but nothing runs check wiring, capacitor and compressor.
- No defrost jumper DFT to R, short the speed-up pins (timer runs 256x faster; 90 min setting takes about 21 s).
- Still no defrost confirm 24 V on T1 (fed once Y is on and switches are closed).
- During forced defrost, expect 24 V between C and W2; afterwards remove the DFT jumper or the unit will defrost every interval for the full 10 minutes.
- A stuck-closed defrost thermostat gives a 10-minute defrost every interval; stuck open means no defrost.
Applies to: KeepRite split heat pumps using FAST 1173636, 1177927 or 1190281 defrost boards
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Defrost Control Boards / Troubleshooting (FAST 1173636/1177927/1190281). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.