Rheem · Heat pump troubleshooting

Outdoor fan runs but compressor does not

What is going on

Before opening the outdoor unit, kill the power at the disconnect and discharge the capacitor, because it can bite. On this Rheem 2-stage heat pump, the outdoor fan is turning but the compressor sits silent, maybe humming. A fan that runs tells you the contactor is pulling in and voltage is reaching the unit. So now you're down to the capacitors, the start relay, the connections and the compressor itself. Don't condemn the compressor until you've cleared the cheap parts and given a hot overload time to reset.

Likely causes

  • Bad run or start capacitor
  • Bad start relay
  • Loose connection at the contactor or compressor terminals
  • Compressor stuck, grounded, open winding or open internal overload
  • Low voltage at the unit

Check in this order

  1. Shut off power at the disconnect, discharge and test the run and start capacitors and the start relay, and replace faulty parts
  2. With power on and the unit calling, check voltage at the compressor and tighten any loose connections, hot terminals or burnt wire ends mean a bad connection
  3. If the internal overload is open, wait at least 2 hours for it to reset before condemning the compressor
  4. Check winding resistance between the terminals and to ground with power off, an open reading or a ground reading means the compressor has failed
  5. Low voltage correct the supply, start kit components are factory installed
  6. If the compressor is bad, refrigerant recovery and replacement is a job for a licensed technician

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 18.6 General Troubleshooting Chart, p.47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.