Trane · General troubleshooting

No Heat

XR203

What is going on

Use the diagnostic click test to see whether the thermostat is sending the heat call.

Likely causes

  • System not set to Heat
  • Loose connection at thermostat or system
  • Heating system needs service or the thermostat needs replacing

Check in this order

  1. Set the thermostat to Heat
  2. Check that the thermostat and system wires are secure
  3. Set the system to Heat and raise the set point above room temperature
  4. Within five minutes the thermostat should make a soft click and Heat On should show. If it does not click, try the reset. If it still does not click, replace the thermostat
  5. If it clicks, have the furnace manufacturer or a service person check that the heating system works

Applies to: Trane XR203 heating systems

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR203 installation and user guide, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.