Trane · General troubleshooting

Call for Service icon is shown

XR202TCONT202

What is going on

Icon appears when the system cannot reach setpoint or the thermostat is faulty.

Likely causes

  • Heating cannot reach within 10 degrees of setpoint within 2 hours
  • Cooling cannot reach within 10 degrees of setpoint within 2 hours
  • Room temperature shows -- so the thermostat needs replacing
  • No buttons respond

Check in this order

  1. For heating, follow the No Heat guide.
  2. For cooling, follow the No Cool guide.
  3. If room temperature shows --, replace the thermostat.
  4. If no buttons respond, check that keypad lockout is not on (lock icon).

Applies to: Trane XR202 / TCONT202

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD51D1-1C-EN Installation and User Guide, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.