Trane · General troubleshooting

No Cool

XR203

What is going on

Use the diagnostic click test to see whether the thermostat is sending the cool call.

Likely causes

  • System not set to Cool
  • Loose connection at thermostat or system
  • Cooling system needs service or the thermostat needs replacing

Check in this order

  1. Set the thermostat to Cool
  2. Check that the thermostat and system wires are secure
  3. Set the system to Cool and lower the set point below room temperature
  4. Within five minutes the thermostat should click. Up to five more minutes of delay is possible if compressor lock-out is set in the installer menu (item 50)
  5. If it does not click after a reset, replace the thermostat

Applies to: Trane XR203 cooling systems

More general guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR203 installation and user guide, p. 19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.