Daikin · Furnace troubleshooting

Thermostat shows communication error or equipment not recognized

Daikin One+

What is going on

The thermostat reports a communication error or does not recognize the equipment after installation.

Likely causes

  • Thermostat terminals 1, 2, C, R are wired incorrectly to the indoor or outdoor unit.
  • Data line voltage is wrong between Data 1 and Data 2.
  • Connector pairing on the indoor or outdoor unit does not match the thermostat terminals.

Check in this order

  1. Check the wiring against the terminal pairing for the system type.
  2. Check voltage between Data 1 and Data 2, expecting about 0.6 VDC.
  3. Check the 9 pin or 7 pin connector position on the indoor or outdoor unit board.
  4. Check the voltage again after wiring is complete.

Applies to: Daikin One+ with communicating indoor or outdoor units

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin One+ installation & commissioning, p. 15-16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.