Carrier · Furnace troubleshooting
Burners will not light or stay lit - Carrier 58SB0A/58SB1A
What is going on
Ignition-proving problems (codes 34 and 14) worked through with the component test.
Likely causes
- Gas valve or manual shutoff off
- Igniter or harness open
- No 24 V to gas valve or valve stuck
- Low inlet pressure or poor carryover
- Dirty, grounded or weak flame sensor
- Control fault
Check in this order
- Check the gas valve switch and the manual shutoff, the green/yellow ground to sheet metal, and that the flame sensor is not touching ground.
- Remove the R lead and run the component test; the igniter should glow orange/white by the end of its 15 s warm-up.
- No glow unplug the igniter harness and check for 115 V from pin 1 to neutral during the test; voltage present means replace the igniter or harness, none means replace the control.
- Put R back and call for heat; the gas valve should get 24 V. No 24 V: check wiring, then the control.
- 24 V but no gas flow: replace the valve. Gas flows but no ignition: check inlet pressure, firing rate, burner carryover gap (about .045 in.).
- Burners light then drop measure flame current; typical is 4.0-6.0 microamps. Under 0.5 microamps: clean the sensor with fine steel wool or replace it.
- If current is normal and burners still drop out, replace the control.
Applies to: Carrier 58SB0A, 58SB1A
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier 58SB0A-05SI installation manual (text export), Fig. 51 Troubleshooting Guide (code 34 branch). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.