Rinnai · Combi boiler troubleshooting
Vent termination near an openable window or door (Canada, TB-200)
What is going on
Rinnai bulletin TB-200 (10/2024) changed Reference B in the I-Series Plus termination clearance tables for Canadian installs to match CSA B149.1. Older printed manuals show the old value.
Likely causes
- Termination placed using the old Reference B value
- Inspector flags clearance to an openable window or door
Check in this order
- Applies to direct vent (concentric and twin pipe, Table 15 Ref. B) and room-air / non-direct vent (Table 23 Ref. B) terminations.
- Clearance from the termination to a window or door that can be opened, Canada:
- Input up to 10,000 Btu/h 6 in. (15 cm).
- Over 10,000 up to 100,000 Btu/h 12 in. (30 cm).
- Over 100,000 Btu/h 36 in. (91 cm).
- Use the boiler's rated input from the rating plate to pick the line. Move the termination if it is too close.
- The same bulletin softens the maintenance warning wording (annual inspection is now 'recommended'); a licensed tech still does all repairs.
Applies to: I-Series Plus combi IP060160C to IP199199C and heat-only IP060S to IP199S, Canadian installations
More combi boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai Technical Bulletin TB-200 (10/2024), I-Series Plus Boiler Manual Revisions for Termination Clearances and Maintenance Warning, p.1-2. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.