Rinnai · Combi boiler troubleshooting

Vent termination near an openable window or door (Canada, TB-200)

I-Series Plus 150K and smallerI-Series Plus 175K and higher

What is going on

Rinnai bulletin TB-200 (10/2024) changed Reference B in the I-Series Plus termination clearance tables for Canadian installs to match CSA B149.1. Older printed manuals show the old value.

Likely causes

  • Termination placed using the old Reference B value
  • Inspector flags clearance to an openable window or door

Check in this order

  1. Applies to direct vent (concentric and twin pipe, Table 15 Ref. B) and room-air / non-direct vent (Table 23 Ref. B) terminations.
  2. Clearance from the termination to a window or door that can be opened, Canada:
  3. Input up to 10,000 Btu/h 6 in. (15 cm).
  4. Over 10,000 up to 100,000 Btu/h 12 in. (30 cm).
  5. Over 100,000 Btu/h 36 in. (91 cm).
  6. Use the boiler's rated input from the rating plate to pick the line. Move the termination if it is too close.
  7. The same bulletin softens the maintenance warning wording (annual inspection is now 'recommended'); a licensed tech still does all repairs.

Applies to: I-Series Plus combi IP060160C to IP199199C and heat-only IP060S to IP199S, Canadian installations

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai Technical Bulletin TB-200 (10/2024), I-Series Plus Boiler Manual Revisions for Termination Clearances and Maintenance Warning, p.1-2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.