Viessmann · Air handler troubleshooting
Wire the indoor unit (base unit wiring)
What is going on
Procedure for wiring the indoor unit base unit. Wiring for the base unit only.
Check in this order
- Strip the signal cable to about 1/2 in (12 mm) and strip the wire ends.
- Crimp fork terminals onto each wire end.
- Open the front panel and remove the electric control box cover.
- Thread the power cable and signal cable through the wire outlet.
- Connect each wire to the terminal with the matching label.
- Tighten each fork terminal firmly on its terminal.
- Clamp the cable so it is not loose and does not pull on the terminals.
- Pass the strap through the ferrite core (magnetic ring) and secure it to the cable.
- Keep the interconnection cable away from the copper refrigerant tube.
- Check the wiring against the diagram on the inside of the control box cover.
- Refit the electric box cover.
Applies to: Indoor air handler DLFSAB / DLFLAB
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 9. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.