Viessmann · Air handler troubleshooting

Temperature sensor check

Vitocal IND-A

What is going on

Checks a temperature sensor by its resistance. Figure 17 is for reference only, since the value varies with temperature.

Check in this order

  1. Turn off all power or disconnect all wires to avoid electric shock.
  2. Disconnect the temperature sensor from the PCB.
  3. Measure the sensor resistance with a multimeter.
  4. Compare the reading with the sensor resistance value for that temperature (Fig. 17).
  5. Let the compressor and coil return to normal temperature before operating the unit, to avoid injury.

Applies to: DLFUAA indoor air handler (Vitocal IND-A)

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFUAA service manual, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.