Refrigerant line installation rules
What is going on
Field piping rules for the interconnecting refrigerant lines between indoor and outdoor units. Outdoor units ship with a full R410A charge; charge, line sizing and capacity are based on 25 ft (7.6 m) runs.
Check in this order
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- Do not bury more than 36 in (914 mm) of line. Give buried sections a minimum 6 in (152 mm) vertical rise to the service valves.
- Insulate both lines with at least 1/2 in (12.7 mm) thick insulation; closed-cell is recommended for long lines.
- Isolate the tubing from the building structure so vibration and noise do not transfer.
- For runs over 25 ft (7.6 m), add refrigerant up to the allowable length in the product data.
Applies to: Ductless interconnecting lines, all sizes
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.