Refrigerant line installation limits
What is going on
Basic line limits between the indoor and outdoor units.
Check in this order
- Use R410A only. Outdoor units ship with a full charge; line sizing is based on runs up to 25 ft (7.6 m).
- Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
- For runs over 25 ft, check the product data and add refrigerant up to the allowed length.
- Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Closed-cell is recommended on long lines.
- If line is buried, do not bury more than 36 in (914 mm). Provide at least a 6 in (152 mm) vertical rise to the service valves.
- Isolate the tubing from the building structure so vibration and noise are not transmitted.
Applies to: DLFUAA ductless system refrigerant lines
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: DLFUAA service manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.