Viessmann · Air handler troubleshooting

Refrigerant line installation limits

Vitocal IND-A

What is going on

Basic line limits between the indoor and outdoor units.

Check in this order

  1. Use R410A only. Outdoor units ship with a full charge; line sizing is based on runs up to 25 ft (7.6 m).
  2. Keep the minimum line length between indoor and outdoor units at 10 ft (3 m).
  3. For runs over 25 ft, check the product data and add refrigerant up to the allowed length.
  4. Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Closed-cell is recommended on long lines.
  5. If line is buried, do not bury more than 36 in (914 mm). Provide at least a 6 in (152 mm) vertical rise to the service valves.
  6. Isolate the tubing from the building structure so vibration and noise are not transmitted.

Applies to: DLFUAA ductless system refrigerant lines

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFUAA service manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.