Goodman · Air handler troubleshooting

No electric heat - R-32 air handler heat kit

What is going on

Heat strips do not come on during an auxiliary/emergency heat call.

Likely causes

  • No line voltage to the air handler or heat kit
  • Transformer failure
  • No W signal from the thermostat
  • Contactor/sequencer not closing
  • Open fusible link
  • Open heater element
  • Open limit switch

Check in this order

  1. Check 240 V at the air handler panel; if missing check breakers or fuses and the wiring.
  2. Check 24 V at the transformer secondary; replace the transformer if missing.
  3. Check 24 V on W at the heat contactor; none = thermostat or wiring.
  4. Confirm the contactor(s) close; replace if not. Check line voltage at the contactor(s).
  5. Power off check each fusible link (opens at about 333 F) - find why it opened before replacing; never bypass.
  6. Ohm each heat element; replace open elements.
  7. Check limit switches (open at about 150 F); replace an open limit and look for low airflow.

Applies to: R-32 AMST, AWSF/AWST, ACSF air handlers with electric heat kits

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), Auxiliary Electric Heating flowchart p.48; heater limit/fuse link checks p.34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.