Blower not running - R-32 AMST/AWSF EEM air handler

What is going on

Indoor blower (EEM/constant-torque motor) does not start on a fan, cooling or heat call.

Likely causes

  • No 240 V at the motor
  • No 24 V signal to a motor tap
  • Failed motor or motor module

Check in this order

  1. Warning: Disconnect power before handling motor connectors.
  2. Measure about 240 V across L and N at the motor; if missing, check breaker, fuses and wiring.
  3. Measure 24 V from C to the active speed tap (T1-T5 / T6-T9 or 1-5 depending on model); if missing, confirm the thermostat is calling for fan and check the low-voltage fuse and wiring.
  4. With both line voltage and 24 V present and no rotation, the motor (or its module) has failed - replace it.
  5. When fitting a new motor, keep the belly band clear of the motor vents and form a drip loop in the wiring.

Applies to: R-32 AMST, AWSF/AWST, ACSF air handlers with EEM blower

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), Air Handler EEM Motor flowchart p.47; Checking High Efficiency Motors p.27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.