Indoor unit power and signal wiring

Vitocal IND-A

What is going on

Wire the indoor unit with the power supply and the signal cable, keeping the signal cable separate from refrigerant parts.

Check in this order

  1. Turn off and lock out the main disconnect before working on the unit.
  2. Strip the signal cable to about 1/2 in (12 mm) and strip the conductors. Crimp fork terminals on the ends.
  3. Open the front panel and remove the electric control box cover.
  4. Run the power and signal cables through the wire outlet.
  5. Connect each fork terminal to its matching terminal and match the wire labels. Tighten each screw firmly.
  6. Check the wiring diagram on the control box cover for the serial number and wire labels.
  7. Clamp the cable so it is not loose and does not pull on the fork terminals.
  8. Keep the interconnection cable away from copper tubing. Keep wires clear of the refrigerant circuit, which can get very hot.
  9. Reattach the electric box cover.

Applies to: DLFUAA indoor unit, all sizes

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFUAA service manual, p. 8. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.