PC 11 Outdoor unit main board DC bus high voltage protection

High severity Vitocal IND-A

What the control is telling you

The DC bus voltage on the outdoor main control board is too high. This shares the PC 01 voltage diagnosis page.

Applies to: Models 18XAK, 24XAK, 30XAK, 36XAK, 48XAK, 60XAK

Likely causes

  • Abnormal DC bus voltage
  • Faulty reactor
  • Faulty IPM board or outdoor PCB
  • Loose wiring

Test and repair steps

  1. Check the power supply and wiring connections.
  2. Measure the voltage between P and N and compare it with the PC 01 values.
  3. Check the reactor; replace it if faulty.
  4. Replace the IPM board or outdoor PCB if the readings are wrong and the reactor is good.

Other codes on the same units

  • EH0E Water-level alarm malfunction
  • EH61 Open or short circuit of temperature sensor (indoor)
  • EH62 Open or short circuit of temperature sensor (indoor)
  • EH65 Open or short circuit of temperature sensor (indoor)
  • PC 08/44/49 Quick maintenance error code
  • PC 10 Outdoor unit low AC voltage protection
  • PC 10/11/12 Quick maintenance error code
  • PC 12 Outdoor unit main board DC bus high voltage protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFUAA Service Manual (Viessmann Vitocal IND-A), p. 27. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.