EL 0C Refrigerant leakage detected

High severity Vitocal IND-O

What the control is telling you

Operation lamp flashes 8 times, timer lamp off. The outdoor unit detects a refrigerant leak. The check only runs in COOLING mode and helps prevent compressor damage from a leak or overload. The manual's text also refers to this as EC; the table prints EL 0C.

Applies to: DLFSOAH09XAK, DLFSOAH18XAK indoor units

Likely causes

  • Refrigerant leak
  • Coil temperature sensor T2 shows no or very little change while the compressor runs

Other codes on the same units

  • EH 3A External fan DC bus voltage too low
  • EH 3b External fan DC bus voltage too high
  • EH 60 Indoor room temperature sensor T1 open or shorted
  • EH 61 Evaporator coil temperature sensor T2 open or shorted
  • EH b3 Communication error between wired controller and indoor unit
  • EH bA Communication fault between external fan module and indoor unit
  • EL 01 Indoor / outdoor unit communication error
  • FH 07 Communication fault between indoor unit and auto-lifting panel

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFSOAH service manual, PDF p. 11, 15. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.