Viessmann · Heat pump

E95 EEPROM failure warning

High severity Vitocal 100-AW AM2V

What the control is telling you

The EEPROM data is incorrect or the EEPROM is damaged.

Applies to: Outdoor unit

Likely causes

  • Burned data is incorrect
  • Read EEPROM data is incorrect
  • EEPROM damaged

Test and repair steps

  1. Replace the inverter board.

Other codes on the same units

  • E83 15 VDC under voltage
  • E84 - E89 Reserved
  • E90 Compressor frequency not being maintained
  • E91 Compressor weak magnetic protection alarm
  • E92 Power unit overheating alarm
  • E93 Reserved
  • E94 AC input current down alarm
  • E96 - E99 Reserved

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.