Viessmann · Heat pump

E613 Communication failure (main board with fan motor module board)

High severity Vitocal 100-AW

What the control is telling you

Communication fault between the main board and the fan motor module board.

Applies to: Vitocal 100-AW AM2V outdoor unit

Likely causes

  • Incorrect connection or poor contact
  • Communication line damaged
  • Main board communication port damaged
  • Fan speed driver board damaged

Test and repair steps

  1. Check the connections between main board, terminal block and display.
  2. Connect the fan board directly to the main board to see if the fault clears; if it clears, replace the communication line.
  3. With power on, measure the voltage change between the A and B ports on the main board; if there is little or no change (about 0.1 V), the communication port is damaged.
  4. If the above checks are normal, replace the fan speed driver board.
  5. Replace the main board if its communication port is damaged.

Models that show this code

7 models in Vitocal 100-AW

0200280340043034043051078AM2V 020028AM2V 034043AM2V 051078

Other codes on the same units

  • E312 Anti-freeze protection, 3 times
  • E510 EVI outlet temp failure
  • E511 Discharge temp failure
  • E513 System 1 pressure sensor failure
  • E514 Low ambient temp failure
  • E515 Outlet temp too low protection
  • E611 Fan 1 failure
  • E612 Fan 2 failure

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 80. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.