Viessmann · Heat pump

E612 Fan 2 failure

High severity Vitocal 100-AW

What the control is telling you

Fan 2 communication or power fault.

Applies to: Vitocal 100-AW AM2V outdoor unit

Likely causes

  • Fan parameter setting incorrect
  • Abnormal connection
  • Fan communication fault
  • Main board communication fault
  • Fan module or inverter driver board faulty
  • Fan damaged

Test and repair steps

  1. Check that the fan parameters are correct.
  2. Confirm the communication connections are correct and secure per the circuit diagram.
  3. With power on, measure the voltage change between the A and B ports on the main board; if there is little or no change (about 0.1 V), the communication port is damaged.
  4. Measure the voltage between the red and black fan terminals on the fan driver board; it should be 200 to 370 V.
  5. Measure the voltage between the white and black fan terminals on the fan driver board; it should be 13.5 to 16.5 V.
  6. Replace the motor if the above checks are normal.
  7. Reset the fan selection parameters, plug and unplug terminals, replace the main control panel, or replace the fan speed or inverter driver board as indicated.

Models that show this code

7 models in Vitocal 100-AW

0200280340043034043051078AM2V 020028AM2V 034043AM2V 051078

Other codes on the same units

  • E312 Anti-freeze protection, 3 times
  • E510 EVI outlet temp failure
  • E511 Discharge temp failure
  • E513 System 1 pressure sensor failure
  • E514 Low ambient temp failure
  • E515 Outlet temp too low protection
  • E611 Fan 1 failure
  • E613 Communication failure (main board with fan motor module board)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 80. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.