Viessmann · Heat pump
E52 Coil temp failure
What the control is telling you
Coil 1 temperature sensor circuit is open, shorted or the sensor is damaged.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- Open circuit or short circuit of the coil 1 temperature sensor
- Coil 1 temperature sensor damaged
Test and repair steps
- Check the connection and resistance of the coil 1 temperature sensor.
- Reconnect the sensor if the connection is faulty.
- Replace the coil 1 temperature sensor if it is damaged.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 77. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.