Viessmann · Heat pump
E43 Outlet water temp too low, 3 times
What the control is telling you
Outlet water temperature too low, occurred 3 times (repeat of E515). Requires manual reset of the outdoor unit.
Applies to: Vitocal 100-AW AM2V outdoor unit
Likely causes
- Repeat of E515 outlet temperature too low fault
Test and repair steps
- Work through the E515 troubleshooting steps.
- Manually reset the outdoor unit after the fault is cleared.
Models that show this code
7 models in Vitocal 100-AW
Other codes on the same units
- E38 Water flow protection, 3 times
- E39 Electric heating protection, 3 times
- E40 Discharge over heat protection, 3 times
- E42 Inlet/outlet water temp difference exceeded, 3 times
- E44 Outlet water over temperature protection, 3 times
- E50 Inlet water temp failure
- E51 Outlet water temp failure
- E52 Coil temp failure
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-AW AM2V installation, service and operating instructions, p. 76. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.