Viessmann · Heat pump

A2L A2L sensor fault

High severity Vitocal 100-WA

What the control is telling you

A2L sensor has reached end of life, failed or is disconnected.

Applies to: Vitocal 100-WA display

Likely causes

  • Sensor end of life
  • Sensor failure
  • Sensor disconnected

Test and repair steps

  1. Check the A2L sensor connection.
  2. Replace the sensor if it has failed or reached end of life.

Models that show this code

5 models in Vitocal 100-WA

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

Other codes on the same units

  • CON Condensate level too high
  • FrE Freeze protection active
  • GAS A2L gas leak
  • HI Compressor high speed
  • HOP High over pressure
  • LO Compressor low speed
  • LUP Low under pressure
  • NSU Not set up

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 48. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.