Viessmann · Boiler

F E2 Gas pressure switch 2 (GDW2) did not close or gas shortage / valve leak

Critical severity Vitocrossal 300 CA3B Dual Fuel

What the control is telling you

GDW2 did not close during self-diagnostics, or there is a gas shortage at GDW2 during the valve leak test.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Likely causes

  • Gas valve does not open
  • Gas valve leaking
  • Gas pressure switch faulty
  • Shortage of gas to gas pressure switch 2 during valve leak test

Test and repair steps

  1. Check the setting of gas pressure switch 2.
  2. Check the connecting cable.
  3. Replace the gas valve if the valve does not open or leaks.

Models that show this code

41 models in Vitocrossal 300 CA3B Dual Fuel

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Other codes on the same units

  • F 82 Secondary boiler water temperature sensor short circuit (A or B)
  • F 83 Secondary boiler water temperature sensor drift (A or B)
  • F 89 Secondary boiler water temperature sensor lead break (A or B)
  • F E0 Gas inlet valve not tight (dual fuel)
  • F E1 Gas pressure switch 2 (GDW2) closed on pressure rise

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 28. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.