Viessmann · Boiler

F 83 Secondary boiler water temperature sensor drift (A or B)

Medium severity Vitocrossal 300 CA3B Dual Fuel

What the control is telling you

Burner control unit enters fault state.

Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Likely causes

  • Sensor drift in secondary boiler water temperature sensor (A or B) or burner control unit

Test and repair steps

  1. Check the lead and sensors A and B.
  2. Replace the sensor if required.

Models that show this code

41 models in Vitocrossal 300 CA3B Dual Fuel

2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0

Other codes on the same units

  • F 82 Secondary boiler water temperature sensor short circuit (A or B)
  • F 89 Secondary boiler water temperature sensor lead break (A or B)
  • F E0 Gas inlet valve not tight (dual fuel)
  • F E1 Gas pressure switch 2 (GDW2) closed on pressure rise
  • F E2 Gas pressure switch 2 (GDW2) did not close or gas shortage / valve leak

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 28. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.