Viessmann · Boiler

F.986 Parameter plausibility check failed between burner 1 and burner 2

Medium severity Vitocrossal 200 CI2

What the control is telling you

The system is in a fault state because the parameter check between burner 1 and burner 2 failed.

Applies to: Vitocrossal 200 CI2

Likely causes

  • Parameters between the two burners do not match

Test and repair steps

  1. Restart the boiler.

Models that show this code

21 models in Vitocrossal 200 CI2

100015002000399500750CI2 1000CI2 1500CI2 1500/2000CI2 2000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750

Other codes on the same units

  • F.896 Safety chain 1 has responded
  • F.897 Safety chain 2 has responded
  • F.920 MZIO function fault, digital input 1
  • F.921 MZIO function fault, digital input 2
  • F.922 MZIO function fault, digital input 3
  • F.971 Gas fitting replaced, calibration value not entered
  • F.982 No heating or DHW: heating circuit 1 pump running dry
  • F.99 PlusBus communication error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 74. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.