Viessmann · Boiler

F.762 System pressure too low

High severity Vitodens 200-W B2HE

What the control is telling you

System in a fault state.

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Likely causes

  • Low water pressure
  • Expansion tank
  • Safety chain plug

Test and repair steps

  1. Top up with water and vent the system.
  2. If repeated, check the minimum pressure switch with an external gauge.
  3. Check expansion tank pre-charge.
  4. Check safety chain plugs on the BCU.

Models that show this code

3 models in Vitodens 200-W B2HE

B2HE-120B2HE-150B2HE-85

Other codes on the same units

  • F.71 Fan speed too low
  • F.72 Fan idle state not reached
  • F.73 BCU internal communication error
  • F.74 Water pressure too low, burner locked out
  • F.763 Gas pressure too high
  • F.764 Lag boiler reports a fault
  • F.765 Lead boiler communication error
  • F.77 BCU data memory error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.