F.74 Water pressure too low, burner locked out
What the control is telling you
Burner locked out and internal pump off; no heating or DHW.
Applies to: Vitodens 200-W B2HE 85, 120, 150, 199
Likely causes
- Low system pressure
- Leak
- Expansion tank pre-charge
- Pressure sensor fault
Test and repair steps
- Top up with water and vent the system.
- If repeated check system pressure sensor with an external gauge.
- Check expansion tank pre-charge.
- Check target system pressure and range settings.
Models that show this code
3 models in Vitodens 200-W B2HE
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitodens 200-W B2HE 85/120/150/199 Service Instructions 6167 813-24 (09/2026), Fault messages, p.62-73. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.