Trane · General
Steam light solid yellow Not making rated steam output
What the display is showing
The humidifier runs but has made less than rated capacity for 168 hours because of low water conductivity. It turns green once output reaches rating.
Applies to: EHUMD800ASM00BA, EHUMD800BSMLCBA
Good to know
- Low conductivity supply water (supply should be 125 to 1,250 uS/cm, about 3 to 36 grains/gal)
What to do
- Check the water type. The 120V units and new canisters can take several days to reach rated output.
- If supply water is very soft, ask about the 8043LCRP canister.
Models that show this code
2 models in Trane steam humidifier EHUMD800
Other codes on the same units
- Fill light flashing green Pulsing valves to clear mineral build-up
- Fill light solid green Filling canister
- Fill light solid red Canister cannot fill, humidifier shut down
- On/Off light flashing green Start-up delay after power restored
- On/Off light solid green Humidifier on
- Service light flashing red Canister at end of life
- Service light solid red Over-current fault, humidifier shut down
- Steam light solid green Making steam, normal
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane steam humidifier owner's manual 32-5092-3A, Display Panel, Table 1; Installation Options & Water Characteristics, PDF p.6-9. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.