Service light flashing red Canister at end of life

Medium severity Trane steam humidifier EHUMD800

What the control is telling you

The canister is worn out. This shows after the unit has run at least 168 hours plus another 24 hours at under 75% of maximum current. The humidifier keeps running at reduced output.

Applies to: EHUMD800ASM00BA, EHUMD800BSMLCBA

Likely causes

  • Mineral build-up on the electrodes

Test and repair steps

  1. Turn off power at the disconnect before opening the unit. Steam and canister water can reach 212F.
  2. Replace the canister with genuine 8043RP (typical water) or 8043LCRP (low conductivity water and 120V units, never with softened water).
  3. Wet the new O-ring with water only, no oil or grease.
  4. Reconnect the two large electrode wires and the one water level probe wire, and check the drain line and steam hose slope.

Models that show this code

2 models in Trane steam humidifier EHUMD800

EHUMD800ASM00BAEHUMD800BSMLCBA

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Trane steam humidifier owner's manual 32-5092-3A, Display Panel, Table 1, PDF p.8-9 (printed p.8-9). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.