Trane · General
Fill light solid red Canister cannot fill, humidifier shut down
What the control is telling you
The canister needs water but will not fill. The unit shuts down when the high water probe sees no water after the fill valve has been on for 40 minutes.
Applies to: EHUMD800ASM00BA, EHUMD800BSMLCBA
Likely causes
- No water supply (saddle valve closed)
- Clogged fill valve strainer
Test and repair steps
- Turn off power at the disconnect before opening the unit. Steam and canister water can reach 212F.
- Make sure the water saddle valve is open.
- If water flow from the fill valve is weak, disconnect the inlet fitting, pull the in-line strainer with a small screwdriver, and clean or replace it.
- Check that the high water probe wire is on its post on the canister.
Models that show this code
2 models in Trane steam humidifier EHUMD800
Other codes on the same units
- Drain light flashing green Preparing to drain
- Drain light solid green Draining canister
- Fill light flashing green Pulsing valves to clear mineral build-up
- Fill light solid green Filling canister
- On/Off light flashing green Start-up delay after power restored
- On/Off light solid green Humidifier on
- Service light flashing red Canister at end of life
- Service light solid red Over-current fault, humidifier shut down
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Trane steam humidifier owner's manual 32-5092-3A, Display Panel, Table 1, PDF p.8-9 (printed p.8-9). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.