831 Indirect tank call running too long

Medium severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

The indirect DHW tank has been calling for more than 12 hours without cycling off.

Applies to: I-Series Plus Solo boilers — 150K BTU and smaller and 175K BTU and higher

Likely causes

  • Indirect tank too small for DHW demand
  • Tank thermistor mounted too low or near cold inlet
  • Primary-secondary piping not used
  • Supply temperature not above tank set temperature (Parameter 30)
  • Faulty tank thermistor or wiring

Test and repair steps

  1. Check that the tank is large enough for the hot water demand; a larger tank may be needed.
  2. Check thermistor placement — if it is too low in the tank or too close to the cold inlet, the pump keeps running after most of the tank has recovered.
  3. Confirm primary-secondary piping is used (low loss header, closely spaced tees, etc.).
  4. Make sure the supply temperature to the tank is higher than the tank set temperature (Parameter 30).
  5. Compare performance data 30 with a thermometer at the same spot; over 5° difference means continue, -40 means unplugged or bad connection.
  6. Inspect the thermistor harness for loose, broken or damaged connections.
  7. Measure tank thermistor resistance and compare against Appendix D in the source manual (p.55).
  8. Replace the thermistor if damaged or defective; see code 371 for more on the indirect tank thermistor.

Models that show this code

6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060SIP090SIP120SIP150SIP175SIP199S

Other codes on the same units

  • 540 High exhaust (flue gas) temperature
  • 610 Combustion fan motor speed fault
  • 700 PC Board fault
  • 710 Gas solenoid circuit – valve position mismatch
  • 720 Flame rod fault
  • 763 0-10V external control input over-voltage
  • 890 Freeze condition detected
  • 999 PC Board / software mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.43. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.