Rinnai · Boiler

710 Gas solenoid circuit – valve position mismatch

High severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

The board checked the gas valve position and it does not match the commanded position.

Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)

Likely causes

  • PC Board gas shut-off DIP switch set to ON
  • Loose, broken or damaged gas solenoid wiring
  • Gas solenoid out of spec
  • Failed gas solenoid valve assembly
  • Failed PC Board

Test and repair steps

  1. Make sure the PC Board DIP switch is OFF (default); when ON it electronically closes the main gas solenoid and triggers 710.
  2. Inspect the gas solenoid harnesses back to the PC Board for loose, broken or damaged connections.
  3. Warning: Turn off electrical, gas and water supply before the following steps.
  4. At PC Board connector CN8, measure black pin #11 to yellow pin #12: 15–25 ohms or 11–14 VDC.
  5. Replace the gas solenoid valve assembly if the readings are incorrect.
  6. If that doesn't fix it, replace the PC Board.
  7. Before swapping the PC Board, write down all parameter settings, then copy them from the old board using the data transfer cable supplied with the new board (see the part's instructions).
  8. If data transfer fails, re-program all parameters and set gas valve values per the Installation and Operation Manual (150K and smaller: also see docs 800000253 and 800000254).

Models that show this code

6 models in I-Series Plus 150K and smaller, I-Series Plus 175K and higher

IP060SIP090SIP120SIP150SIP175SIP199S

Other codes on the same units

  • 540 High exhaust (flue gas) temperature
  • 610 Combustion fan motor speed fault
  • 700 PC Board fault
  • 720 Flame rod fault
  • 763 0-10V external control input over-voltage
  • 831 Indirect tank call running too long
  • 890 Freeze condition detected
  • 999 PC Board / software mismatch

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.