Rheem · Heat pump
L29 High pressure control lockout
What the control is telling you
HPC opened three (3) times during the same call; the ICC locks out the compressor and alternates L and 29. Manual reset required. (Table text wrongly says 'LPC has opened' for L29.)
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Dirty outdoor coil or outdoor fan not running (cooling)
- Dirty indoor coil/filter or indoor blower not running (heating)
- Liquid line restriction
- Refrigerant overcharge
Test and repair steps
- Work through the code 29 checks.
- Read stored faults press TEST and SW2 together for 1 second (insulated probes); up to 6 faults scroll, newest first.
- Reset the ICC after the cause is fixed press TEST for 1 second with an insulated probe (preferred), or cycle 24VAC (pull R or C) or cycle line power.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.4 Active Compressor Protection Mode / 12.6 ICC Diagnostic Codes, p.25, 30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.