NTI · Boiler
Hold 27 Flame rod shorted to ground
What the control is telling you
The flame sensing circuit sees a dead short to ground. A short to ground can also show up as a flame circuit timeout (Lockout 113).
Applies to: Trinity Tft60, Tft85, Tft110, Tft154, Tft201, Tft285, Tft340, Tft399
Likely causes
- Flame circuit shorted to ground (zero-ohm short shows as this code, high-resistance shorts show as Lockout 113)
- Blocked condensate drain flooding the burner area
- Outside voltage present on the R or CH terminals
- 4-20 mA input above 21 mA
Test and repair steps
- Make sure the condensate drain and trap are not blocked
- Confirm no outside voltage is applied to the R and CH terminals
- If a 4-20 mA signal is used, keep it at or below 21 mA
Models that show this code
13 models in Trinity Tft
Other codes on the same units
- Hold 25 Internal fault: Spark voltage changed too much during flame sensing time
- Hold 26 Internal fault: Static flame ripple
- Hold 26 Internal fault: Static flame ripple
- Hold 27 Flame rod shorted to ground
- Hold 28 Internal fault: A/D linearity test fails
- Hold 28 Internal fault: A/D linearity test fails
- Hold 29 Internal fault: Flame bias cannot be set in range
- Hold 29 Internal fault: Flame bias cannot be set in range
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI Trinity Tft399 Installation and Operation Manual (2018-09-07), Sec. 16.0 Troubleshooting, Table 16-3. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.