NTI · Boiler
01 03 Insufficient circulation or low water pressure
What the control is telling you
Supply temperature rising faster than 12.6 °F per second, seen three times. Manual reset.
Applies to: TRX150
Likely causes
- Low water pressure
- Air in the CH circuit
- Faulty temperature probe or pump
Test and repair steps
- Press Reset to clear the code.
- If it returns, check the water pressure on the gauge.
- Purge air from the central heating circuit.
- Check that the supply and return probes work and are positioned correctly.
- Check that the circulation pump works and is positioned correctly.
Models that show this code
5 models in TRX
Other codes on the same units
- 01 01 Overheat (CH circuit)
- 01 04 Insufficient circulation or low water pressure
- 01 05 Insufficient circulation or low water pressure
- 01 06 Insufficient circulation or low water pressure
- 01 07 Insufficient circulation or water
- 01 08 Low water pressure lockout (water pressure switch)
- 1 10 CH flow temperature probe open or short circuit
- 1 12 CH return temperature probe open or short circuit
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 90. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.