01 01 Overheat (CH circuit)

Critical severity TRX

What the control is telling you

Central heating circuit overheat. Clears with a manual reset.

Applies to: TRX150

Test and repair steps

  1. Press Reset to clear the code.
  2. If it returns, check that the supply and return temperature probes work and are positioned correctly.
  3. Check that the circulation pump works and is positioned correctly.
  4. Check the water pressure on the pressure gauge.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 01 03 Insufficient circulation or low water pressure
  • 01 04 Insufficient circulation or low water pressure
  • 01 05 Insufficient circulation or low water pressure
  • 01 06 Insufficient circulation or low water pressure
  • 01 07 Insufficient circulation or water
  • 01 08 Low water pressure lockout (water pressure switch)
  • 1 10 CH flow temperature probe open or short circuit
  • 1 12 CH return temperature probe open or short circuit

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 90. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.